37
List of Alarms and Troubleshooting
For all alarms conditions, the troubleshooting steps provided in this chapter are suggested actions to take in the event of
an alarm. Follow all site policy procedures set by local governing agencies in the case of a spill, leak, or malfunction. If
the steps provided by this manual or the site policy are followed and the system still requires additional support, contact
Franklin Fueling Systems Technical Services.
The * (asterisk) symbol indicates that there may be a variation in the event. The part, or test type application event, is
indicated by the actual alarm you receive.
Displayed Alarm /
Warning
Device Description Recommended Actions
2-Wire Sensor Module is
Ofine
Slot 2-Wire Sensor Module is
ofine due to unknown
causes.
Follow safety procedures before working inside of the console. Visually
verify a steady, green “Run” light. If a red “Err” light is ashing or steady,
try to reboot the system. If the condition still exists, contact Franklin
Fueling Systems’ Technical Services Dept. for support on this issue.
2-Wire Sensor Module
Setup Error
None Programming errors made
during setup of the 2-Wire
Sensor Module.
Verify 2-Wire Sensor Module programming parameters. If the condition
still exists, contact Franklin Fueling Systems’ Technical Services Dept. for
support on this issue.
3-Wire Sensor Module is
Ofine
Slot 3-Wire Sensor Module is
ofine due to unknown
causes.
Follow safety procedures before working inside of the console. Visually
verify a steady, green “Run” light. If a red “Err” light is ashing or steady,
try to reboot the system. If the condition still exists, contact Franklin
Fueling Systems’ Technical Services Dept. for support on this issue.
3-Wire Sensor Module
Setup Error
None Programming errors made
during setup of the 3-Wire
Sensor Module.
Verify 3-Wire Sensor Module programming parameters. If the condition
still exists, contact Franklin Fueling Systems’ Technical Services Dept. for
support on this issue.
4-20mA Input Error ChannelANA Errors detected on the
inputs of the 4-20mA Input
module.
Follow safety procedures before working inside of the console. Verify
that programming parameters meet site specications. Check all wiring
associated with the input at fault. Test operation of 4-20mA device. If
the condition still exists, contact Franklin Fueling Systems’ Technical
Services Dept. for support on this issue.
4-20mA Module is Ofine Slot 4-20mA Module is ofine
due to unknown causes.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If a red “Err” light is ashing or steady,
try to reboot system. If the condition still exists, contact Franklin Fueling
Systems’ Technical Services Dept. for support on this issue.
4-20mA Module Setup Error None Programming errors made
during setup of the 4-20mA
Module.
Verify 4-20mA Module programming parameters. If the condition still
exists, contact Franklin Fueling Systems’ Technical Services Dept. for
support on this issue.
AC Input Module is Ofine Slot AC Input Module is ofine
due to unknown causes.
Follow safety procedures before working inside of the console. Visually
verify a steady green “Run” light. If a red “Err” light is ashing or steady,
try to reboot system. If the condition still exists, contact Franklin Fueling
Systems’ Technical Services Dept. for support on this issue.
AC Input Module Setup
Error
None Programming errors made
during setup of the AC Input
Module.
Verify AC Input Module programming parameters. If the condition still
exists, contact Franklin Fueling Systems’ Technical Services Dept. for
support on this issue.
Air in Line Line ELLD detects air in line.
Where and how?
Alpha volume correction
error
Tank This error is caused my a
programming mistake in the
Special Products section.
Verify Special Product Alpha volume correction program parameters.
API volume correction error Tank This error is caused my a
programming mistake in the
Special Products section.
Verify Special Product API volume correction program parameters.
Controller Module is Ofine Slot Controller Module is ofine
due to unknown causes.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is ashing or steady
try to reboot system. If the condition still exists, contact Franklin Fueling
Systems’ Technical Services Dept. for support on this issue.
Controller Module Setup
Error
None Programming errors
made during setup of the
Controller Module.
Verify Controller Module programming parameters. If the condition still
exists, contact Franklin Fueling Systems’ Technical Services Dept. for
support on this issue.
Correction table error Tank Level and Volume mismatch
detected in Correction table
programming.
Verify that all levels and volumes are entered accurately into the
Correction Table programming.