
13
Fuel Management Systems (FMS) Line Application Set-Up
Setting up the lines establishes which transducer and relay is used on the specic line and allows the user to change
certain parameters in the operation of the line leak testing. Make sure the line is holding at or above the minimum required
pressure (see page 5). If the pressure is too low, review the check-valve used, and adjust the pump / pump controller for
proper pressure.
Parameter Parameter Value
Number of lines Number of product lines
Name Text box, name each channel to easily identify in the mapping.
Submersible Pump Module Select either power supply module or relay module depending upon which relay is being used for
pump control, or if TPI is being used. If Power Supply Board is selected and a relay from this power
supply board was associated to a pump, an additional option will show up to indicate if TPI or relay
will be used.
Submersible Pump Channel Select the channel that the submersible controller is connected to.
Transducer Select the transducer installed in the line.
Enabled Select yes
Pressure Up Test Wait Time * Default is 4 Seconds. This is the time that the gauge waits for the line to pressure up above 12 PSI.
Catch Pressure Wait Time * Default is 2 seconds. This is the time the gauge waits after the pump turns off to make sure the
pressure is at least 12 PSI.
Dispenser Pressure Test When selected, this gauge monitors the line pressure while dispensing. If the pressure decreases to
7.5 PSI, the line goes into alarm mode. The pump shuts off and is disabled.
Gross / Monthly / Annual Tests
Enable
Select Yes. This allows the LS500 to run the tests.
Wait Period Between Tests Default setting is 0 days. (This is the scheduling for line test after the test passed).
Shutdown on Test Fail If selected, this will shut down the submersible if that line fails that type of test
* These settings typically will not need to be changed. Contact FFS tech support before changing these settings.
Example: LS500 Application Setup
Group Name Parameter Name Parameter Value
Lines Number of lines 3
Line 1 Name Unleaded Line
Submersible Pump Module Relay Module
Submersible Pump Channel Unleaded STP
Transducer Unleaded Transducer
Enabled Yes
Pressure Up Test Wait Time 4 Sec
Catch pressure Wait Time 2 Sec
Dispenser Pressure Test Yes
Gross Tests Enable Yes
Monthly Tests Enable yes
Wait Period Between Passed Tests 0 Days
Shutdown on Failed Test
Annual Tests
Enable Yes
Wait Period Between Passed Tests 0 Days
Shutdown on Failed Test
Note: Do not enable the line in set-up until the transducers have been properly connected to the 4-20 Input Module.
Comentarios a estos manuales