LS-500 Alarms and Warnings
Alarms During the Learn Process
Alarm Symptom Possible Cause Resolution
Failed to pressure up STP is not turning on Verify that the 4-20 transducer is 
a relay / TPI input
Check the programming
Is the pump controller powered 
on?
Check the controller
If controlled by a relay, is the 
common of the relay wired to 110 
Volts?
Test the voltage on the relay 
common
Is another STP turning on? Check the other STPs
STP is turning on, but 
the LS500 doesn’t see 
the pressure change
Is the 4-20 transducer in alarm? Check alarms
Is the wrong transducer 
mapped?
Check programming
Is the clamp valve down? Look at the pressure gauge on 
the needle valve kit for operating 
pressure
Line is not 
congured
Program mapping error Verify programming
Program error 
detected
Console software error Reboot console
Air in line Console has sensed line 
pressure variations
Investigate, then Purge Line Starting 
at the Furthest Dispenser
Not learned Learn Line (FMS > Control 
> Lines > Learn) follow learn 
procedures
Follow learn procedures
Insufcient volume Line is too small
Leak generator not correct
Air in the line
Check line size
Review leak generator set-up
Purge air from the line
Alarms During Operation
Alarm Symptom Possible Cause Resolution
Failed to pressure 
up
Pressure was less 
that 12 psi after 
programmed delay 
when STP turned on
Clogged STP intake Investigate, force a manual test 
and observe pressure
STP is not turning on Verify that the transducer is 
programmed as an input for the 
relay / TPI.
Check the programming
Is the pump controller powered 
on
Check the controller
If controlled by a relay, is the 
common of the relay wired to 
110 V
Test the voltage on the relay 
common
Is another STP turning on? Check the other STPs
STP is turning on, but 
the LS500 doesn’t see 
the pressure change
Is the 4-20 transducer in alarm? Check alarms
Is the wrong transducer mapped Check programming