Catastrophic leak Investigate for leaks
Is the clamp valve down Look at the pressure gauge on 
the needle valve kit for operating 
pressure
Test Result Condition Possible Cause Resolution
Failed to catch 
pressure
Pressure was less 
that 12 psi after 
programmed delay 
when STP turned off 
Check valve damaged Investigate, force a manual test 
and observe pressure
Dispenser solenoid is still open
after hook signal is off
Dispense, release hook, keep 
nozzle open
Catastrophic leak Investigate for a catastrophic leak 
such as a pipe breaking
Sudden Pressure 
Loss
Pressure dropped to 
less than 5 psi
Catastrophic leak Monitor line pressure using a 
pressure gauge, investigate for 
leaks
Dispensing Pressure 
Test Failed
Pressure dropped to 
less than 7.5 psi while 
dispensing
Monitor line pressure using a 
pressure gauge, investigate for 
leaks
High Pump Pressure Pressure was above 
50 psi during the catch 
pressure test 3 times 
consecutively
Monitor line pressure using a 
pressure gauge, investigate for 
faulty check valve
Extended Hook 
Signal
Hook signal was applied 
for more than 4 hours
Dispenser hook signal on steady Verify that all handles are down, 
test AC inputs to determine which 
is giving a signal
Pressure Transducer 
Fail
Communication failure 
to transducer
Wiring Check wiring connections at the 
console, junction box and quick 
disconnect. 
Transducer failure Direct connect, if still in alarm, 
replace.
Air in line Console has Sensed 
Line Pressure Variations
Line left open or air elimination 
loop failing
Investigate, then Purge Line 
Starting at the Furthest Dispenser
Not Enabled Line disabled Either manually, or by another 
application shut the STP down
Check other alarms, nd source of 
interruption
Marginal Pass of 
Gross Leak Test
Passing result of gross 
test, but marginally
Line is not thermally stable Force a gross leak test
Pump Request 
Ignored
STP did not turn on 
when requested
Controller not functioning
System is busy
TPI problem Check RS485 communication
STP is disabled by another 
application
4-20 mA Input error Contact Technical Support
Module is Ofine Communication failure 
between the control 
module and the module 
ofine
Look at module LEDs Red, replace module. 
Green solid or ashing, power 
down the console and re-seat the 
module
Operating Alarms (Continued)